VDI 2035: water quality in heat pumps and heating systems

Informative and educational content, prepared by Q-Tech from public sources and from the data declared by manufacturers. It is not technical or legal advice. Legal notice and sources at the end of the article.

On 18 June 2025, Q-Tech attended a dedicated training session on VDI 2035 in Granada, at the invitation of Domusa Teknik and Sertegra. It was given by Andoni Catalán of Aquateknika Ingeniería Aplicada (Donostia). VDI 2035 is the German guideline on water in heating systems. This article brings together its values and what they mean for a heat-pump system.

1. What VDI 2035 is

Key pointWhat it says
PublisherVDI (Verein Deutscher Ingenieure), the Association of German Engineers
Current editionPart 1, March 2021. It incorporates the former Part 2 (corrosion): scale and corrosion are now covered in a single document
ScopeWater-based heating systems to EN 12828, with flow temperatures up to 100 °C
Outside its scopeCircuits with antifreeze (glycol) and district heating networks (in Germany, AGFW FW 510). Chilled-water and cooling circuits have their own guideline, VDI 6044
StatusA technical guideline, not a law. Many manufacturers of heat generators and pumps cite it in their manuals and warranty terms
In SpainThere is no equivalent standard with mandatory values. There is the report UNE 112076 IN, "Prevention of corrosion in water circuits"

2. The four water values

The guideline distinguishes two modes of operation: low-salt, the recommended one, and saline, which allows higher conductivity in exchange for much less oxygen.

ParameterLow-salt (recommended)Saline
Electrical conductivity at 25 °CAbove 10 and up to 100 µS/cmAbove 100 and up to 1,500 µS/cm
Dissolved oxygenBelow 0.1 mg/lBelow 0.02 mg/l
pH without aluminium8.2 to 10.08.2 to 10.0
pH with aluminium alloys8.2 to 9.08.2 to 9.0
AppearanceClear, free of sedimentClear, free of sediment
Total hardnessDepends on the system output and litres per kW (section 3)
The four VDI 2035 values: conductivity, pH, dissolved oxygen and total hardness, with tap-water oxygen against the limit and when to measure
VDI 2035 at a glance. By Q-Tech. Tap to enlarge.
ItemReading
Fill waterTo run low-salt, the system is filled with demineralised water, normally below 10 µS/cm at the unit outlet
When to measure pH8–12 weeks after filling: the water self-alkalises during that time. Measuring tolerance: ± 0.2
pH below 7.5A sign of higher corrosion risk: find the cause
Oxygen in tap waterAbout 9 mg/l at 20 °C in contact with air: some 90 times the low-salt limit
Documents older than 2021Still in circulation with pH 8.2–8.5 for aluminium and the old hardness table. Check which edition each source cites

3. How hard the water may be

The maximum hardness depends on two figures: the total output and the specific system volume. This is the total water volume of the system divided by the output of the smallest heat generator, in litres per kW.

Total heating outputUp to 20 l/kWAbove 20 and up to 40 l/kWAbove 40 l/kW
Up to 50 kW, generator with 0.3 l/kW or moreNo requirement16.8 °dH (30 °fH) maximumBelow 0.3 °dH
Up to 50 kW, generator with less than 0.3 l/kW or with electric heating elements16.8 °dH (30 °fH) maximum8.4 °dH (15 °fH) maximumBelow 0.3 °dH
Above 50 and up to 200 kW11.2 °dH (20 °fH) maximum5.6 °dH (10 °fH) maximumBelow 0.3 °dH
Above 200 and up to 600 kW8.4 °dH (15 °fH) maximumBelow 0.3 °dHBelow 0.3 °dH
Above 600 kWBelow 0.3 °dHBelow 0.3 °dHBelow 0.3 °dH

Conversions: 1 mol/m³ = 5.6 °dH = 10 °fH; 0.3 °dH is about 0.5 °fH. In Spain hardness is given in French degrees or in mg/l of CaCO₃ (1 °fH = 10 mg/l).

VDI 2035 total hardness traffic-light table by output and litres per kW, with two 8 kW heat-pump examples
Total hardness by output and litres per kW. By Q-Tech. Tap to enlarge.
Heat-pump exampleVolumeLitres per kWMaximum hardness
8 kW heat pump, 200 l buffer and 100 l of circuit300 l37.5 l/kW16.8 °dH (30 °fH); with an electric backup heater, 8.4 °dH (15 °fH)
The same heat pump with 400 l in total400 l50 l/kWBelow 0.3 °dH: demineralised water
RuleWhat it means
Changes in 2021Full softening moves from 0.11 to 0.3 °dH, and applies from 40 l/kW instead of 50. Requirements become stricter up to 40 l/kW
Total water addedThe table applies as long as fill and top-up water do not exceed 3 times the system volume
Top-upIf more than 10 % of the volume is topped up, find the cause. Hence the water meter on the fill line
Hardness times litresThe risk depends on hardness and on the litres added: soft water topped up many times brings in as much lime as hard water added once

Reading: with a buffer tank and underfloor heating, a domestic heat-pump system easily exceeds 40 l/kW. In that case the guideline calls for demineralised water.

4. Why heat pumps are more sensitive to water

A current system combines narrow water passages and mixed materials: steel, copper, brass, stainless steel, aluminium and plastics.

FactorWhat happensReference figure
OxygenIt enters with the fill water, with every top-up and by diffusion through plastic pipes, even when the circuit is under pressureDIN 4726: a barrier pipe lets through no more than 0.32 mg/(m²·day) at 40 °C. A pipe without a barrier, about 50 times more: over 200 days, like changing the water about 100 times
Magnetite sludgeIt forms only if oxygen gets in (Grundfos). The rotor of permanent-magnet pumps attracts it until they blockFirst step: find the air inlet or the leak
ScaleIt insulates heat-exchange surfaces and promotes under-deposit corrosionRule of thumb from heat-pump manufacturers (Alpha Innotec): 1 mm of scale, about 10 % less efficiency. Calcium carbonate conducts about 2.2 W/(m·K); copper, around 400
Galvanic corrosionThe less noble metal corrodes when it touches a nobler one and the water carries currentSmall anode and large cathode: fast attack. Lower conductivity weakens the "cable", which is the water. A dielectric union breaks the contact
ComponentsPlate heat exchangers, short-stroke valves and flow meters tolerate little dirtGrundfos recommends water that meets standards such as VDI 2035
Glycol (outside VDI 2035)As it degrades through heat, oxygen or contact with copper or aluminium, it forms acids and lowers the pHIndustry references: unused inhibited glycol, pH 9.0–9.5; below 8, inhibitor running out; below 7, drain, clean and refill
Diagram of a heat-pump system showing where oxygen, scale, galvanic corrosion, magnetite and glycol act, with the galvanic series
What damages a closed circuit and where. By Q-Tech. Tap to enlarge.

Indicative galvanic series, in seawater and in volts against the calomel electrode: magnesium −1.60; zinc −1.03; aluminium alloys −0.79; carbon steel −0.61; copper −0.36; passive 316 stainless steel −0.05. It ranks the metals; it is not for calculation.

5. Softening is not demineralising

Water softenerDemineralisation (mixed bed)
What it removesCalcium and magnesium, exchanged for sodiumPractically all salts
ConductivityStays the same or risesFalls: allows low-salt operation
pHCan exceed 10 in service and damage seals (Alpha Innotec manuals)Some resins keep it within the guideline range
With aluminiumThe guideline does not recommend full softeningCompatible, with pH between 8.2 and 9.0
ReadingSolves scale and leaves the system in saline mode, the most demanding on oxygenSolves scale and conductivity at the same time
VDI 2035 calculator: check whether your system water meets the guideline. Open the calculator

6. Heating water to VDI 2035 in five steps

Five steps for heating water to VDI 2035: measure, clean, fill, keep oxygen out and record, with common mistakes
Method for new and existing systems. By Q-Tech. Tap to enlarge.
StepWhat to do
1. Measure and calculateHardness and conductivity of the tap water, total volume, litres per kW and circuit materials, especially if there is aluminium
2. CleanIn existing systems: fine filtration and a magnetic separator in bypass, with the heating running, until the water runs clear
3. Fill correctlyDemineralised water to stay below 100 µS/cm, with the pH within the guideline range
4. Keep oxygen outBarrier pipes, a correctly sized expansion vessel and no uncontrolled automatic filling. A microbubble air vent does not remove dissolved oxygen
5. Monitor and recordWater meter on the fill line and a system logbook. Measure after 8–12 weeks and every year

Chemical additives remain an exception and are always documented. One example of equipment for these steps is the range from magnetic (Germany), distributed in Spain by Aquateknika. According to the manufacturer, its mobile filter combines a 1 µm filter with a neodymium separator and works in bypass without stopping the heating. Its HWR plus regulator combines a degasser, a filter and a magnesium anode that consumes dissolved oxygen.

7. The manufacturer's manual prevails

VDI 2035 is the reference, but each manufacturer sets its own values. If its manual asks for more, the manual prevails.

Manufacturer and unitHardnessConductivitypHOther
Daikin Altherma EHS(X/H) (2021 manual)Up to 3 mmol/lUp to 1,500 µS/cm (ideally up to 100)6.5 to 8.5Chlorides and sulphates up to 250 mg/l
LG Therma V (commissioning)4 to 8.5 °dH10 to 500 µS/cm7.5 to 9.0Iron up to 0.2 mg/l
Wolf (boilers with aluminium)As per VDI 2035Below 100 or 800 µS/cm8.2 to 9.0 in mixed systemsNo antifreeze or inhibitors
Grundfos (pumps)Refers to standards such as VDI 2035

Data from each manufacturer's manuals. The ranges do not match each other or the guideline: Daikin's pH of 6.5 to 8.5 falls outside the 8.2–10.0 of VDI 2035.

8. And in Spain

SituationReading
Soft tap waterNot enough. Tap water in Málaga city leaves the plant at 95–100 mg/l of CaCO₃ (EMASA, 2021), about 10 °fH, but with hundreds of µS/cm: the system would run in saline mode
Hard tap waterAbove 30 °fH, a heat pump of up to 50 kW fails the table from 20 l/kW; with electric heating elements, at any volume
Top-upsEvery litre of tap water adds lime and oxygen. Without a meter, nobody knows how much water has gone in
ReferencesReport UNE 112076 IN and the informative annex on corrosion of UNE-EN 1264-4 (underfloor heating)

What to do and what to avoid

SituationOptionAvoid
New heat-pump system with buffer tankCalculate the litres per kW and fill with demineralised waterFilling with tap water without measuring it
Existing system with sludgeClean and filter in bypass before changing the waterRefilling without removing the magnetite
Circuit with aluminiumpH between 8.2 and 9.0Full softening without pH control
Automatic fillingWater meter and a record of top-upsTopping up without knowing how much or why
Circuit with glycolFollow the glycol manufacturer and measure the pHApplying VDI 2035, which does not cover it
Guideline and manual disagreeMeet the stricter one, normally the manualA can of "anti-corrosion" added by eye

Heat pumps with Q-Tech

Q-Tech advises on and integrates the heat pump with the controls, domestic hot water and the other systems in the home. It is also supplied as a pre-assembled plant room. More models in heat-pump systems.

To discuss a project: Q-Tech on WhatsApp or info@q-tech.es.

Legal notice on this content

Purpose. This article summarises, for purely informative, educational and outreach purposes, the requirements of the VDI 2035 guideline on water in heating systems and how they apply to heat pumps. It is based on the VDI 2035 training given by Aquateknika in Granada on 18 June 2025, which Q-Tech attended at the invitation of Domusa Teknik and Sertegra. Values as per the March 2021 edition of VDI 2035.

Origin of the information. The content has been prepared from the public sources listed below, from published summaries of the guideline and from the data declared by manufacturers in their manuals. Q-Tech's calculation examples are indicative.

Scope. It is not technical, legal or professional advice, and it does not replace the official text of VDI 2035, the manufacturer's documentation or the assessment of each system by a competent engineer. Data may change and the content may contain errors or omissions. It does not guarantee the condition or service life of any specific system.

Liability. Before filling, treating or maintaining a system, the requirements must be checked against the current text of the guideline, the manufacturer's manual and a professional. Q-TECH HOUSES DIVISION S.L.UNIP. accepts no liability for decisions taken solely on the basis of this content.

Trademarks and images. The trademarks and trade names mentioned belong to their owners and are used only to identify products and sources. Texts and infographics: © Q-TECH HOUSES DIVISION S.L.UNIP. (q-tech.es). They may be quoted with a link to this page; full reproduction or modification requires prior permission.

Sources consulted

  • VDI 2035 Part 1 (March 2021), as summarised by BWT, Grünbeck, SYR, Reflex, Elysator and UWS ("Heizwasseraufbereitung nach VDI 2035").
  • Aquateknika Ingeniería Aplicada: VDI 2035 training, Granada, 18 June 2025, at the invitation of Domusa Teknik and Sertegra. magnetic GmbH & Co. KG: "Heating Water Treatment" brochure (2020) and mobile filter and HWR plus data sheets.
  • DIN 4726: oxygen-tight plastic pipes. Oxygen solubility tables for water.
  • Alpha Innotec: heat-pump manuals (water quality and effect of scale). Grundfos: water-quality recommendations for circulator pumps.
  • Daikin: Altherma EHS(X/H) manual (2021). LG: Therma V water requirements. Wolf: heating-water requirements.
  • Hydratech and ChemAqua: glycol degradation and pH control.
  • EMASA: Málaga water quality (2021). AENOR: UNE 112076 IN and UNE-EN 1264-4.