* Screwed connection PN10. For flange connection, consultr.
Advantages
- Energy savings due to greater system efficiency with the Q-Limit function (volume flow limiter)
- Improved Energy Efficiency Index (EEI) ≤ 0.20 for all single pumps
- Enhanced display for better readability and ease of operation
- Space-saving installation thanks to compact design and variable-orientation LC display
- Modular concept for connection of all conventional bus systems (e.g. Modbus, BACnet, CAN, LON and PLR)
- Tried-and-tested quality and reliability
Construction
Glandless circulator with threaded connection or flange connection, EC motor with automatic power adjustment.
Application
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulation systems.
Function
Manual functions
- Setting the operating mode
- Differential pressure setpoint setting
- Setting automatic setback operation
- Setting the pump ON/OFF
- Setting the speed (manual control mode)
Automatic functions
- Continuous power adjustment according to the operating mode
- Automatic setback operation
- Deblocking function
- Soft start
- Full motor protection with integrated trip electronics
External control functions
- "Overriding Off" control input (possible with Stratos IF-Modules)
- "Overriding Min" control input (possible with Stratos IF-Modules)
- "Analogue In 0 - 10 V" control input (remote speed adjustment) (possible with Stratos IF-Modules)
- "Analogue In 0 - 10 V" control input (remote setpoint adjustment) (possible with Stratos IF-Modules)
Signal and display functions
- Collective fault signal (potential-free NC contact)
- Individual run signal (potential-free NO contact) (possible with Stratos IF-Modules)
- Fault signal light
- LCD display for indication of pump data and error codes
Data exchange
- Infrared interface for wireless data exchange with IR-Stick/IR-Monitor
- Modbus RTU serial digital interface for connection to building automation BA via RS485 BUS system (possible with Stratos IF-Modules)
- BACnet serial digital interface MS/TP Slave for connection to building automation BA via RS485 BUS system (possible with Stratos IF-Modules)
- CAN serial digital interface for connection to building automation BA via CAN BUS system (possible with Stratos IF-Modules)
- LON serial digital interface for connection to a LONWorks network (possible with Stratos IF-Modules)
- PLR serial digital interface for connection to BA via Wilo interface converter or company-specific coupling modules (possible with Stratos IF-Modules)
Dual puma management (twit-head puma or 2 x single pumps)
- Main/standby operation (automatic fault-actuated switchover/time-dependent pump cycling): various combinations with Stratos IF-Modules (accessories) possible
- Parallel operation (efficiency-optimised peak load activation and deactivation): various combinations with Stratos IF-Modules (accessories) possible
Scope of delivery
- Pump
- Including thermal insulation
- Including gaskets for threaded connection
- Including washers for flange screws (for nominal connection diameters DN 32 - DN 65)
- Including installation and operating instructions
Technical data
- Permissible temperature range -10 °C to +110 °C
- Mains connection 1~230 V, 50/60 Hz
- Protection class IPX4D
- Screwed connection or flange connection (depending on type) Rp 1 to DN 100
- Max. operating pressure of standard version: 6/10 bar or 6 bar (special version: 10 bar or 16 bar)
Materials
- Pump housing: grey cast iron with cataphoretic coating
- Thermal insulation: polypropylene
- Shaft: Stainless steel
- Bearing: carbon, metal impregnated
- Impeller: Plastic
Description
- Glandless circulator with EC motor and integrated automatic power adjustment
- Green Button Technology and graphic display
- Motor protection with trip electronics
- Plug connection for functional extension with optional IF module for building automation (BA)
- Impeller with three-dimensionally curved blades and plastic sealing tube made of carbon fibre composite material